Reading APC Microlink descriptors
---------------------------------

//////////////////////////////////////////////////////////////////////////////
// This chapter documents the on-the-wire structure the "apcmicrolink" driver
// parses, for anyone extending its variable maps to cover more of a device.
//////////////////////////////////////////////////////////////////////////////

Overall concept
~~~~~~~~~~~~~~~

A Microlink device publishes a machine-readable *descriptor* alongside its
data, so the driver learns where each value lives instead of hard-coding
offsets. `drivers/apcmicrolink-maps.c` therefore maps *descriptor paths* to NUT
variable names, and the driver resolves those paths to byte offsets at run
time.

Everything below was derived from a live APC SCL500RMI1UC. Other models share
the structure but not necessarily the same set of usages.

Frames, pages and the blob
~~~~~~~~~~~~~~~~~~~~~~~~~~

A record is `[page id][width data bytes][2 byte checksum]`. The `width` comes
from page 0, along with the page count, so a device with `width = 32` and
96 pages has 35-byte records and a 3072-byte address space.

The driver assembles those pages into one flat blob by laying page N at byte
offset `N * width`. Page 0 also carries a *descriptor table offset* (byte 12 on
the device above) and a pointer to where the *data region* begins. Everything
before that pointer is the descriptor program; everything after it is live
data. Do not assume the descriptor comes second - on the SCL500RMI1UC the
descriptor occupies pages `0x00`-`0x3F` and data starts at page `0x40`.

Path syntax
~~~~~~~~~~~

Paths look like SNMP OIDs and behave like them:

    <object> : <collection> . <sub-collection> . <attribute>

for example `2:4.5.9.40` - object `2`, collection `4.5`, sub-collection `9`,
attribute `40`. Components are hexadecimal without a prefix.

Attribute IDs are scope-relative
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

This is the single most useful property when identifying an unknown usage:
*within one top-level object*, a trailing attribute ID means the same thing on
whichever collection carries it.

[options="header"]
|===============================================================================
| Attribute | Seen at                                              | Meaning
| `.F.69`   | `2:4.5`, `2:4.6`, `2:4.7`, `2:4`                     | total time
| `.40`     | `2:4.9`, `2:4.5.9`                                   | serial number
| `.42`     | `2:4.9`, `2:4.5`                                     | part number
| `.4A`     | `2:4.5.9`                                            | firmware revision
| `.19`     | `2:4.9`, `2:4.5`                                     | a date
| `.82`     | `2:4`, `2:4.3E`                                      | name
| `.31`     | `2:4.5`, `2:4.3E`                                    | low runtime warning
| `.25`     | `2:4.6`, `2:4.7`                                     | voltage
| `.27`     | `2:4.6`, `2:4.7`                                     | frequency
| `.11`     | `2`, `2:4.5`                                         | test result
| `.13`     | `2`, `2:4.5`                                         | calibration result
|===============================================================================

Known collections under object `2` (the UPS itself):

    2:4.5    battery          2:4.9    inventory
    2:4.6    input            2:4.B    user interface
    2:4.7    output / power   2:4.3E   outlet group
    2:4.8    authentication   2:4.F    statistics

`9` (inventory) and `F` (statistics) nest inside other collections, which is
why `2:4.5.9.40` is the battery serial and `2:4.6.F.69` the input total time.

WARNING: Top-level objects have *independent* attribute namespaces. Do not
carry a meaning from object `2` into object `3`: on the same device `3:22` is a
temperature threshold rather than a temperature, `3:25` is input sensitivity
rather than a voltage, and `3:26` is accumulated energy rather than a current.
Object `2` is the UPS device tree and `3` appears to be a system or controller
object; `4`, `5` and `A` are not yet identified.

Two scopes, one NUT name
~~~~~~~~~~~~~~~~~~~~~~~~

Because the same attribute exists at several scopes, it is easy to map two
usages onto one NUT variable by accident. When that happens the winner depends
on the order usages appear in the descriptor, not on the order of entries in
the map - so the result varies by device and is not reproducible.

Where a device may populate either scope, map the specific one and promote the
general one only when the specific is absent. `microlink_publish_test_result()`
does this for `ups.test.result`: `2:4.5.11` is mapped directly, and `2:11` is
published under an experimental name and copied over only if the battery-scope
usage is missing entirely.

Identifying an unknown usage
~~~~~~~~~~~~~~~~~~~~~~~~~~~~

In rough order of cost:

1. *Infer from the attribute ID.* If the trailing component is already known at
   another scope in the same object, that is very likely its meaning. Costs
   nothing.

2. *Diff a reference client's writes.* Change one setting in the vendor's own
   software while capturing the bus, then look for host-to-device frames that
   are not the plain control bytes. A write frame names its page and offset
   directly, so it identifies the usage with no guesswork - and proves the
   field is writable at the same time. This is far more reliable than matching
   values by coincidence.

3. *Cross-reference an SNMP agent.* Vendor management software often ships an
   SNMP agent serving a documented MIB. Walking it gives named, described
   values that can be matched against the data pages, which is useful for
   read-only fields that step 2 cannot reach.

Mapping pitfalls
~~~~~~~~~~~~~~~~

*Check the units `docs/nut-names.txt` states, not just the name.* Several
usages are enumerations whose NUT counterpart is numeric. `ups.test.interval`
is defined as seconds, but the device reports a schedule enum - two of whose
members ("never", "on start-up only") have no interval at all. Publishing the
enum string there would break any client doing arithmetic on it.

*Beware percentages reported as if they were absolute.* A fixed-point field
that reads roughly a hundred times too small is more likely a percentage of a
nominal rating than a wrong binary point - a wrong binary point is off by a
power of two, never by 5. Cross-multiplying independent readings catches this
quickly: output current times output voltage should agree with apparent power.

*Descriptor usages can be marked skipped.* Skipped usages are published neither
under a name nor in the `unmapped` listing, so a value visible in a page dump
may have no corresponding variable at all. Check the skip flag before assuming
a mapping is missing.